20-35 kV SC(B) Series Dry-Type Power Transformer

Epoxy-resin cast dry-type transformers for 20 kV and 35 kV grids, stepping down to 0.4–10 kV for direct supply to users.

  • Rated capacity: 50–25,000 kVA
  • Rated voltage: 20–38.5 kV (HV side)

Request a Quote

Description

Overview

This series of products are used to reduce the power supply of 35kV and 20kV power grid to 400V power distribution power supply or 10kV power transmission power supply directly for users. The main advantages are:
1. Reduce the land occupation and the construction of multilevel substation project, which has
significant social benefits.
2. Save the project investment and improve the economic benefit.

3. Reduce 10kV transmission and transformation links, so that operation and maintenance
costs significantly reduced.
4. The use of high voltage small current instead of low-voltage large current transmission, reduce line loss, reduce the operation cost of the line.

5. 35kV, 20kV power directly into the power supply center, effectively improving the reliability of power supply.

Technical Parameters

1) 20kV SC(B) 10 Series Excitation Regulated Distribution Transformer

Rated Capacity (kVA) Voltage combination(kV) Connection-group code No-load current % No-load loss W Load loss (120℃)W Impedance%
H.V. High voltage tapping range % L.V.
50 20 22 24 ± 5 ± 2 ×2.5 0.4 Dyn11 Yyn0 1.2 340 1230 6.0
100 1.1 535 1980 6.0
160 1.0 670 2360 6.0
200 0.8 730 2930 6.0
250 0.8 835 3400 6.0
315 0.7 960 4060 6.0
400 0.6 1140 4820 6.0
500 0.6 1330 5760 6.0
630 0.5 1510 6800 6.0
800 0.5 1730 8220 6.0
1000 0.5 2040 9730 6.0
1250 0.5 2360 11480 6.0
1600 0.5 2760 13790 6.0
2000 0.5 3200 16280 6.0
2500 0.4 3820 19270 6.0
3150 0.4 4300 23610 7.0

2) 20kV SC(B)11 Series Excitation Regulated Distribution Transformer

Rated Capacity (kVA) Voltage combination(kV) Connection-group code No-load current % No-load loss W Load loss (120℃)W Impedance%
H.V. High voltage tapping range % L.V.
50 20 22 24 ± 5 ± 2 ×2.5 0.4 Dyn11 Yyn0 1.2 300 1230 6.0
100 1.1 470 1980 6.0
160 1.0 580 2460 6.0
200 0.8 640 2930 6.0
250 0.8 720 3400 6.0
315 0.7 840 4060 6.0
400 0.6 1000 4820 6.0
500 0.6 1170 5760 6.0
630 0.5 1320 6800 6.0
800 0.5 1520 8220 6.0
1000 0.5 1790 9730 6.0
1250 0.5 2060 11480 6.0
1600 0.5 2410 13790 6.0
2000 0.5 2800 16290 6.0
2500 0.4 3340 19270 6.0

3) 35kV SC (B) 10 Series Excitation Voltage Distribution Transformer

Rated Capacity (kVA) Voltage combination(kV) Connection-group code No-load current % No-load loss W Load loss (120℃)W Impedance%
H.V. High voltage tapping range % L.V.
50 35 ~ 38.5 ± 5 ± 2 ×2.5 0.4 Dyn11 Yyn0 2.8 450 1430 6.0
100 2.4 630 2090 6.0
160 1.8 790 2760 6.0
200 1.8 880 3330 6.0
250 1.6 990 3800 6.0
315 1.6 1180 4510 6.0
400 1.4 1380 5420 6.0
500 1.4 1620 6650 6.0
630 1.2 1860 7700 6.0
800 1.2 2160 9120 6.0
1000 1.0 2430 10450 6.0
1250 0.9 2840 12730 6.0
1600 0.9 3150 15490 6.0
2000 0.9 3830 18240 6.0
2500 0.9 4460 21850 6.0

4) 35kV SC(B)10 Series Excitation Regulated Dry-Type Power Transformer

Rated Capacity (kVA) Voltage combination(kV) Connection-group code No-load current % No-load loss W Load loss (120℃)W Impedance%
H.V. High voltage tapping range % L.V.
800 1 35 ~ 38.5 ± 5 ± 2 ×2.5 3.15 6 6.3 10 10.5 11 Dyn11 Yd11 Yyn0 1.1 2250 9400 6.0
1000 1.1 2670 10900 6.0
1250 1.0 3130 12900 6.0
1600 1.0 3690 15400 6.0
2000 0.9 4230 18200 7.0
2500 0.9 4860 21800 7.0
3150 0.8 6030 24500 8.0
4000 0.8 7020 29400 8.0
5000 0.7 8370 34900 8.0
6300 0.7 9900 40800 8.0
8000 Dyn11 Yd11 Ynn11 0.6 11300 46000 9.0
10000 6 6.3 10 10.5 11 0.6 12900 55500 9.0
12500 0.6 15700 64600 9.0
16000 0.6 19300 76000 9.0
20000 0.4 22900 85500 10.0
25000 0.35 27100 101000 10.0

Features

  • High performance, low loss, for the 9 series of products.
  • Choose high quality silicon steel sheet, at the same time, reduce magnetic flux
  • density greatly, reduce the magneto strictive quantity of silicon steel sheet in operation, reduce noise effectively.
  • Optimize the structure of high voltage coil, improve the distribution of interlayer voltage and capacitance, greatly improve the product tolerance of overvoltage, and improve the distribution of electric field, so that the quantity of partial discharge is reduced further.
  • The temperature control system and air cooling device can be configured to
  • automatically start the fan cooling device when the load is too large, and effectively improve the overload capacity of the equipment.

Additional information

Product Family

Dry-Type

Rated Capacity

50–25, 000 kVA

Rated Voltage

20–38.5 kV (HV side)