KYN28A-12 (GZS1) Indoor Metal-Clad Withdrawable Switchgear

Indoor metal-clad withdrawable switchgear with relay compartment, communication interface and five-prevention interlocking.

  • Rated voltage: 3–12 kV, 50 Hz

Request a Quote

Description

Overview

The KYN28A-12 (GZS1) indoor metal-clad withdrawable switchgear is a complete power distribution unit designed for three-phase AC 50Hz systems. It is widely used for receiving and distributing electrical energy in power networks rated from 3 kV to 12 kV, while providing reliable control, protection, and monitoring of electrical circuits.

This switchgear is equipped with a relay compartment that supports the installation of various types of microprocessor-based integrated protection relays, enabling intelligent system control. It features advanced automation functions including remote control, remote measurement, remote signaling, and remote adjustment. With a built-in communication interface, the system can be integrated into a field network via a CAN bus.

The equipment is designed with comprehensive mechanical and electrical interlocking systems, commonly referred to as the “Five Prevention” functions, which ensure operational safety:

  • Preventing incorrect opening or closing of the circuit breaker
  • Preventing withdrawal or insertion of the withdrawable unit under load
  • Preventing closing of the earthing switch when the circuit is energized
  • Preventing energizing the circuit when the earthing switch is in the closed position
  • Preventing access to live compartments

The switchgear can be equipped with VS1 vacuum circuit breakers or optionally configured with imported VD4 vacuum circuit breakers, offering flexibility to meet different application requirements.

Environmental Conditions

The switchgear is designed to operate under the following environmental conditions:

1. Ambient Temperature:
Maximum +40°C, minimum −10°C

2. Altitude:
Not exceeding 1000 m above sea level

3. Humidity:

  • Daily average relative humidity: ≤ 95%
  • Monthly average relative humidity: ≤ 90%

4. Installation Environment:
Free from fire hazards, explosion risks, severe pollution, and corrosive gases that may damage metal or insulation

5. Mechanical Conditions:
Installed in locations without severe vibration or shock, and with a vertical inclination not exceeding 8°

6. Special Conditions:
If the actual service conditions differ from those specified above, consultation between the user and the manufacturer is required

Technical Parameters

Item Unit Data
Rated Voltage kV 3.6, 7.2, 12
Rated Insulation Level – Power Frequency Withstand Voltage (1 min) kV 42/48
Rated Insulation Level – Lightning Impulse Withstand Voltage (Peak) kV 75/85
Rated Frequency Hz 50
Rated Current A 630, 1250, 1600, 2000, 2500, 3150
Rated Short-Time Withstand Current kA/S 20/4, 25/4, 31.5/4, 40/3, 50/3
Rated Peak Withstand Current kA 50, 63, 80, 100, 125
Degree of Protection – Enclosure: IP4X; Circuit breaker compartment (door open): IP2X
Rated Voltage of Closing, Opening and Auxiliary Circuits V DC: 24, 36, 48, 60, 110, 220 AC: 110, 220
Dimension mm 800(1000)x1500x2300

Additional information

Product Family

Switchgear

Rated Capacity
Rated Voltage

3–12 kV, 50 Hz